Three-phase 400V series (0.75 to 11kW) |
Item |
Specifications |
Type (FRN###F1S-4A) |
0.75 |
1.5 |
2.2 |
3.7 |
5.5 |
7.5 |
11 |
Applicable motor rating [kW] (*1) |
0.75 |
1.5 |
2.2 |
3.7 |
5.5 |
7.5 |
11 |
Output
ratings |
Rated capacity [kVA] (*2) |
1.6 |
2.6 |
4.0 |
6.3 |
9.0 |
12 |
17 |
Rated voltage [V] (*3) |
Three-phase 200V to 240V (with AVR function) |
Rated current [A] (*4)(*10) |
2.5 |
3.7 |
5.5 |
9.0 |
12.5 |
16.5 |
23 |
Overload capability |
120% of rated current for 1min, |
Rated frequency [Hz] |
50, 60Hz |
Input
ratings |
Phases,
voltage,
frequency |
Main power supply |
Three-phase, 380 to 480V ,60/50Hz |
Auxiliary control
power input |
Single-phase, 380 to 480V ,60/50Hz |
Auxiliary fan
power input |
- |
Voltage/frequency variations |
Voltage: +10 to -15% (Voltage unbalance (*8): 2% or less) Frequency: +5 to -5% |
Rated current [A] (*9) |
(with DCR) |
1.6 |
3.0 |
4.5 |
7.5 |
10.6 |
14.4 |
21.1 |
(without DCR) |
3.1 |
5.9 |
8.2 |
13.0 |
17.3 |
23.2 |
33.0 |
Required power supply capacity [kVA] (*5) |
1.2 |
2.2 |
3.1 |
5.3 |
7.4 |
10 |
15 |
Braking |
Torque [%] |
20 |
DC injection braking |
Starting frequency: 0.1 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level: 0 to 60% of rated current |
Applicable safety standards |
UL508C, C22.2No.14, EN50178:1997 |
Enclosure (IEC60529) |
IP20, UL open type |
Cooling method |
Natural cooling |
Fan cooling |
Weight / Mass [kg] |
3.1 |
3.2 |
3.3 |
3.4 |
3.4 |
5.8 |
6.0 |
Three-phase 400V series (15 to 55kW) |
Item |
Specifications |
Type (FRN###F1S-4A) |
15 |
18.5 |
22 |
30 |
37 |
45 |
55 |
Applicable motor rating [kW] (*1) |
15 |
18.5 |
22 |
30 |
37 |
45 |
55 |
Output
ratings |
Rated capacity [kVA] (*2) |
22 |
27 |
32 |
43 |
53 |
64 |
80 |
Rated voltage [V] (*3) |
Three-phase 200V to 240V (with AVR function) |
Rated current [A] (*4)(*10) |
30 |
37 |
44 |
59 |
72 |
85 |
105 |
Overload capability |
120% of rated current for 1min, |
Rated frequency [Hz] |
50, 60Hz |
Input
ratings |
Phases,
voltage,
frequency |
Main power supply |
Three-phase, 380 to 480V ,60/50Hz |
Three-phase, 200 to 220V/50Hz
Three-phase, 200 to 230V/60Hz |
Auxiliary control
power input |
Single-phase, 380 to 480V ,60/50Hz |
Single-phase, 200 to 220V/50Hz
Single-phase, 200 to 230V/60Hz |
Auxiliary fan
power input |
- |
*10 |
Voltage/frequency variations |
Voltage: +10 to -15% (Voltage unbalance (*8): 2% or less) Frequency: +5 to -5% |
Rated current [A] (*9) |
(with DCR) |
28.8 |
35.5 |
42.2 |
57.0 |
68.5 |
83.2 |
102 |
(without DCR) |
43.8 |
52.3 |
60.6 |
77.9 |
94.3 |
114 |
140 |
Required power supply capacity [kVA] (*5) |
20 |
25 |
30 |
40 |
48 |
58 |
71 |
Braking |
Torque [%] |
20 |
10 to 15 |
DC injection braking |
Starting frequency: 0.1 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level: 0 to 60% of rated current |
Applicable safety standards |
UL508C, C22.2No.14, EN50178:1997 |
Enclosure (IEC60529) |
IP20, UL open type |
Cooling method |
Fan cooling |
Weight / Mass [kg] |
6.9 |
9.5 |
9.7 |
11.5 |
23 |
33 |
34 |
Three-phase 400V series (75 to 560kW) |
Item |
Specifications |
Type (FRN ###F1S-4A) |
75 |
90 |
110 |
132 |
160 |
200 |
220 |
Applicable motor rating [kW] (*1) |
75 |
90 |
110 |
132 |
160 |
200 |
220 |
Output
ratings |
Rated capacity [kVA] (*2) |
105 |
128 |
154 |
182 |
221 |
274 |
316 |
Rated voltage [V] (*3) |
Three-phase 200V to 240V (with AVR function) |
Rated current [A] (*4)(*10) |
139 |
168 |
203 |
240 |
290 |
360 |
415 |
Overload capability |
120% of rated current for 1min, |
Rated frequency [Hz] |
50, 60Hz |
Input
ratings |
Phases,
voltage,
frequency |
Main power supply |
Three-phase, 380V to 440V, 50Hz ; Three-phase, 380V to 480V, 60Hz |
Auxiliary control
power input |
Single-phase,380V to 480V, 50/60Hz |
Auxiliary fan
power input |
Single-phase, 380V to 440V, 50Hz
Single-phase, 380V to 480V, 60Hz |
Voltage/frequency variations |
Voltage: +10 to -15% (Voltage unbalance (*8): 2% or less) Frequency: +5 to -5% |
Rated current [A] (*9) |
(with DCR) |
138 |
164 |
201 |
238 |
286 |
357 |
390 |
(without DCR) |
- |
- |
- |
- |
- |
- |
- |
Required power supply capacity [kVA] (*5) |
96 |
114 |
140 |
165 |
199 |
248 |
271 |
Braking |
Torque [%] |
20 |
DC injection braking |
Starting frequency: 0.1 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level: 0 to 60% of rated current |
Applicable safety standards |
UL508C, C22.2No.14, EN50178:1997 |
Enclosure (IEC60529) |
IP20, UL open type |
Cooling method |
Fan cooling |
Weight / Mass [kg] |
34 |
42 |
45 |
63 |
67 |
96 |
98 |
Three-phase 400V series (280 to 560kW) |
Item |
Specifications |
Type (FRN ###F1S-4A) |
280 |
315 |
355 |
400 |
450 |
500 |
560 |
Applicable motor rating [kW] (*1) |
280 |
315 |
355 |
400 |
450 |
500 |
560 |
Output
ratings |
Rated capacity [kVA] (*2) |
396 |
445 |
495 |
563 |
640 |
731 |
792 |
Rated voltage [V] (*3) |
Three-phase 200V to 240V (with AVR function) |
Rated current [A] (*4)(*10) |
520 |
585 |
650 |
740 |
840 |
960 |
1040 |
Overload capability |
120% of rated current for 1min, |
Rated frequency [Hz] |
50, 60Hz |
Input
ratings |
Phases,
voltage,
frequency |
Main power supply |
Three-phase, 380V to 440V, 50Hz ; Three-phase, 380V to 480V, 60Hz |
Auxiliary control
power input |
Single-phase,380V to 480V, 50/60Hz |
Auxiliary fan
power input |
Single-phase, 380V to 440V, 50Hz
Single-phase, 380V to 480V, 60Hz |
Voltage/frequency variations |
Voltage: +10 to -15% (Voltage unbalance (*8): 2% or less) Frequency: +5 to -5% |
Rated current [A] (*9) |
(with DCR) |
500 |
559 |
628 |
705 |
789 |
881 |
990 |
(without DCR) |
- |
- |
- |
- |
- |
- |
- |
Required power supply capacity [kVA] (*5) |
347 |
388 |
435 |
489 |
547 |
611 |
686 |
Braking |
Torque [%] |
20 |
10 to 15 |
DC injection braking |
Starting frequency: 0.1 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level: 0 to 60% of rated current |
Applicable safety standards |
UL508C, C22.2No.14, EN50178:1997 |
Enclosure (IEC60529) |
IP20, UL open type |
Cooling method |
Fan cooling |
Weight / Mass [kg] |
162 |
165 |
282 |
286 |
355 |
360 |
360 |